Tel:
+44 (0)121 504 3840
|
|||||||||||
|
Fax:
+44 (0)121 504 3844
|
|||||||||||
|
|
|||||||||||
|
Downflow
Units
|
|
![]() |
Features
|
|
We manufacture chilled water and DX downflow units ranging from 37 through to 220kW cooling capacities. There are 6 different sizes and incorporate high efficiency filters, high sensible duty coils and precision control system. We can build exactly to a customers requirements, with an extensive range of microprocessor controls and in-house software engineers. Optional Inverter motor control for energy saving and flexibility. All units are supplied with Trend LCD panel mounted fascia for both monitoring and setpoint adjustment. The flexible control system is fully capable of remote monitoring or connecting to a propriety Building Energy Management System. |
|
| Technical Data - CTHSC | ||||||
|
Model
|
370
|
560
|
750
|
1160
|
1750
|
2200
|
|
Nominal
Capacity (kW)
|
37
|
56
|
75
|
116
|
175
|
220
|
|
Airflow
at 75Pa ESP (m3/s)
|
1.8
|
2.7
|
3.6
|
6.3
|
8.4
|
10.5
|
|
Humidifier
Capacity (kg/h)
|
3
|
6
|
9
|
9
|
15
|
15
|
|
Electric
Heater (kW)
|
15
|
15
|
15
|
24
|
36
|
48
|
|
Electrical
Data Fans FLC (A)
|
5 | 6 | 8.2 | 16.4 | 16.4 | 24.6 |
|
Electrical
Data Electric Heat FLC (A)
|
21 | 21 | 21 | 33 | 50 | 66 |
|
Electrical
Data Humidifier FLC (A)
|
13 | 26 | 13 | 13 | 21 | 21 |
| Technical Data - CTHSR/Y (DX) | ||||||
|
Model
|
370
|
560
|
750
|
1160
|
1750
|
2200
|
|
Nominal
Capacity (kW)
|
37
|
56
|
75
|
116
|
175
|
220
|
|
Airflow
at 75Pa ESP (m3/s)
|
1.8
|
2.7
|
3.6
|
6.3
|
8.4
|
10.5
|
|
Humidifier
Capacity (kg/h)
|
3
|
6
|
9
|
9
|
15
|
15
|
|
Electric
Heater (kW)
|
15
|
15
|
15
|
24
|
36
|
48
|
|
Electrical
Data Fans FLC (A)
|
7 | 9.4 | 9.4 | 12.4 | 18.6 | 24.8 |
|
Electrical
Data Electric Heat FLC (A)
|
21 | 21 | 21 | 33 | 50 | 66 |
|
Electrical
Data Humidifier FLC (A)
|
13 | 26 | 13 | 13 | 21 | 21 |
|
Electrical
Data Compressors (A)
|
18
|
25
|
32
|
48
|
72
|
96
|
|
For further information please contact us sales@climaticdirect.co.uk |